You are here : Home > Products > Fire prevention
Disc valvesThe database contains 5 articles relating to this field: "Disc valves". Please select from the following popup menu. Fields of application: For preventing the transmission of fire and smoke through ventilation ducts that go across fire lobbies. For installation in walls and ceilings as per DIN 18017 Part 3 (2.2.2).

Volumetric flow range: 15 - 250 m3/h
Function: The fire damper poppet valve with bayonet fixing and the especially developed mounting frame permits easy and rapid cleaning and maintenance. To control the flow rate, the shut-off disc may be rotated manually. The function by means of a safety fuse and non-return device is retained. The fire damper poppet valve complies with resistance class K90. Approval No: Z-41.3-559
Models: Made of sheet steel painted to RAL 9010 (white) |